2402-468 Low Voltage Ground Monitor
This is a low voltage GCS using a 6314-023 monitor with 3108-043 transformer. It incorporates a 24 volt A.C. relay combined with an impedance matching transformer which makes it possible for the relay to "see" small changes of resistance in the pilot/ground circuit. The ground check system utilizes a ratio of 10:1 on the transformer, normally, so that a change of 1 ohm appears as 100 ohms to the relay. It has a manual reset and trip indication. The manual reset feature gives an indication as to what circuit tripped the breaker with the indicating light. This light must be reset manually before operation can resume. It has additional ability to adjust ground loop resistance up to 4.5 ohms from front panel.
- 120 VAC source, 5 VA, 60 HZ
- Push to test switch
- Polarity reversal switch
- Dead front construction
- Front mounted - accessible from the front or outside of the panel
- Trip indication